AC Energy Systems, Inc. Specifications

The Carbon Monoxide Detecting and Ventilation Fan Control System (CO System) including, wiring and conduit, shall be furnished and installed to provide a complete operational system. All conduit, wiring and terminations shall be in accordance with the manufacturer’s printed instructions. All wiring to be in conduit. No exposed wiring is allowed. Starters shall be furnished and installed by others.

CO System shall be microprocessor based utilizing MOS (metal oxide semiconductor) solid state remote sensors as manufactured by Quantum Group, Inc. Contact: AC Energy Systems, Inc. (760) 436-2116.

All periodic calibration and maintenance labor and materials shall be included to cover a period of 12 months from owner’s acceptance of the CO System. Quantum CO Control board shall have a 5-year factory equipment warranty. The plug-in CO module shall have a 2.5-year warranty.

Each CO sensor shall be housed in a lockable, painted, 16 gauge steel enclosure. Enclosure shall have colored panel lights that are labeled: “POWER”, “FAN”, and “ALARM”. An 85-dB audible alarm shall be mounted at each sensor location to alarm if alarm limits are exceeded for 15 minutes of if sensor is in fault.

Each CO sensor shall automatically compensate for temperature and humidity over the range of 32-125 F and 10-90% relative humidity to stabilize the set-point and prevent false alarms.

CO System shall turn fan(s) on when CO level exceeds 25 ppm for more than 3 minutes. Fans shall automatically turn off when CO levels drop below 25 ppm. System shall have a “minimum fan run-time” to allow fan motors to cool off.

Unit shall go into high CO alarm if the CO level exceeds 100 ppm for 15 minutes of the concentration over the previous 8 hours exceeds and average of 25 ppm. Alarms at each sensing unit shall automatically reset when CO concentration levels fall below the alarm level.

Sensors shall be factory pre-calibrated and shall be a plug-in module not requiring and soldering, mechanical fastening or wiring. Unit shall provide an audible signal 60 days prior to expiration of sensor module. If the sensor module is not replaced within 60 days, then the unit shall turn fans on and signal a fault condition.

CO System to provide fail-safe (fans running) operation if control wires are broken, sensor fails, or power is lost to the sensing unit.